Introduction: The Invisible Threat in Multi-Lane Access Control
During the commissioning of high-traffic multi-entry/multi-exit toll islands or systems with multiple parallel barrier gates, engineering teams often encounter an extremely frustrating phenomenon: even when the lane is clearly empty, the barrier gates frequently raise and lower on their own. Faced with these erratic “ghost vehicle” false alarms, many technicians often mistakenly assume that the control board is damaged or the relays have aged, thereby wasting a great deal of time blindly replacing hardware. In reality, the true culprit is not the control board, but rather the fact that adjacent coils buried beneath the road surface are too close together, causing their high-frequency magnetic fields to overlap and triggering severe electromagnetic interference—crosstalk.
To completely eliminate this hidden threat in multi-lane concurrent scenarios, simply re-grooving the road is ineffective; it is essential to intervene at the hardware level to precisely control the vehicle loop detector crosstalk frequency.
This article will use the industrial-grade dual-channel devices, the LD-200 and LD-202 Dual Channel Vehicle Loop Detectors, as our practical reference. We will set aside obscure academic formulas and use the most straightforward engineering logic to break down the physical mechanisms behind coil crosstalk distortion. At the same time, we will provide detailed guidance for field maintenance personnel on how to use the S1 and S2 DIP switches on the device panel to strictly enforce the “frequency interleaving rule” within the 20 kHz to 100 kHz frequency range. Combined with high-precision digital sensitivity matching at an extremely low percentage, this approach fundamentally cuts off the pathways for multi-channel mutual inductance interference, creating a zero-false-alarm defense system for parallel lanes.
The Physics of LC Resonance and Intermodulation Distortion
At high-density, multi-lane entry and exit points, induction loops are not merely ordinary wires buried in asphalt; they are massive antennas that continuously radiate alternating magnetic fields outward. To resolve the frequent false alarms at these sites, electrical engineers must first understand how these invisible magnetic fields “interfere” with one another in physical space.
Understanding Magnetic Crosstalk in Adjacent Lanes
At toll plazas or the entrances to large industrial parks, space constraints often force the loops in adjacent lanes to be positioned very close together. When two adjacent vehicle detectors operate at the same or very similar frequencies, the electromagnetic fields they generate underground cross their respective boundaries, resulting in severe physical overlap.
This phenomenon is known in engineering as intermodulation distortion or crosstalk. You can visualize this intuitively as two people shouting at the top of their lungs in a small room, both using the same pitch. Because the frequencies are so close, the two waves overlap and interfere with each other, producing extremely unstable beat frequency interference. Faced with this chaotic overlap of signals, the microcontroller (MCU) at the base level is simply unable to isolate the true metal-detection signal belonging to its own lane.
Symptoms of Frequency Interference
In real-world field operations, this type of low-level magnetic field crosstalk exhibits extremely obvious symptoms, allowing frontline engineers to quickly troubleshoot and identify the issue based on the following phenomena:
First is the most critical issue: “phantom engagement.” Due to continuous interference from the magnetic field of an adjacent lane, the reference environmental frequency received by the detector’s microprocessor fluctuates wildly up and down. The system misinterprets these sudden frequency changes as a vehicle passing through, causing the relay to frequently trigger a closure signal even when no vehicle is present. This results in the barrier arm performing dangerous “unattended, automatic raising and lowering” movements.
Second is the false alarm involving the panel indicator light. Severe crosstalk significantly distorts the coil’s actual operating frequency, causing the green LED on the detector panel to flash abnormally slowly. According to the device’s low-level error codes, a slow-flashing green light typically indicates a short circuit in the coil or a severe shortage of windings. However, in scenarios with multiple lanes running side by side, if you confirm that the coil is intact, this slow flashing is often a critical warning signal indicating that the frequency has been dragged to the brink of collapse by interference from adjacent lanes.
The Golden Rule of Frequency Alternation (Pitfall 1)
In actual on-site installation, to completely eliminate false triggers caused by vehicle loop detector crosstalk, engineering teams must strictly adhere to one core rule within the control box: frequency alternation.
Why Adjacent Loops Must Use Different Frequencies
Many novice installers, when faced with complex toll plazas, often fall into a critical electrical pitfall: in pursuit of so-called “fastest response” or “best performance,” they habitually set all inductive loop detectors in the distribution cabinet to the highest frequency and highest sensitivity. In scenarios with multiple lanes running side by side, this is nothing short of shooting oneself in the foot.
This “set everything to maximum” approach is the direct cause of erratic barrier gate operation on-site. When the loops of two adjacent lanes are both oscillating in the same high-frequency band (or the same low-frequency band), the frequencies of the electromagnetic waves they emit completely overlap, inevitably causing intense interference and mutual disruption underground. Therefore, the first step in troubleshooting on-site is to dispel this beginner’s misconception and keep in mind an absolute rule: adjacent loops must never operate at the same frequency level.
Planning the 20 kHz–100 kHz Spectrum
To completely eliminate this interference path caused by intermodulation distortion at the physical level, maintenance personnel must scientifically stagger the planning of the 20 kHz to 100 kHz operating frequency band.
The most practical and efficient engineering guideline is the “one high, one low” staggering rule. When deploying multiple parallel lanes in a multi-input, multi-output configuration, technicians must ensure that detectors in adjacent lanes are set to different frequencies. For example, if the detector in Entry Lane 1 is set to “High,” the adjacent Exit Lane 2 must be set to “Low,” followed by Lane 3 set to “High,” and so on.
By configuring this staggered matrix, a frequency difference of at least 20 kHz is enforced between adjacent loops. As long as this frequency difference is maintained, the two magnetic fields operate as if on parallel tracks with different speed limits; the underlying signals do not interfere with one another, thereby completely eliminating multi-channel magnetic coupling crosstalk and ensuring that every barrier-lowering command received by the mainboard is precise and error-free.
LD-200 Frequency Tuning Matrix (S1 & S2 Settings)
Having established the ironclad rule of “one high, one low” frequency interleaving, we now need to implement it precisely in the actual hardware. Industrial-grade dual-channel ground-loop detectors (such as the LD-200) actually incorporate two completely independent high-frequency oscillation circuits. To achieve complete electromagnetic isolation, engineers must use two separate sets of DIP switches (S1 and S2) to tune the front coil (CH1) and rear coil (CH2) independently.

Configuring CH1 Frequency via S1 (DIP 9 & 10)
For setting the frequency of the front channel (CH1), the microprocessor delegates control to the main DIP switch matrix S1 (Switch 1). The two DIP switches at the far right of the S1 panel—DIP 9 and DIP 10—are the key switches that determine the CH1 oscillation frequency. Through the four possible combinations of these two switches, you can force the CH1 operating frequency to range from 20 kHz to 100 kHz.
For example, if you plan to use the front loop of the current lane as a “low-frequency shield,” simply set DIP 9 on S1 to ON and DIP 10 to ON as well; CH1 will immediately be locked to operate in the lower frequency range.
Configuring CH2 Frequency via S2 (DIP 6 & 7)
Frequency control for the rear channel (CH2) is completely physically isolated on the auxiliary DIP switch matrix S2 (Switch 2). On the S2 panel, DIP 6 and DIP 7 are specifically responsible for controlling CH2’s frequency parameters.
If CH1 has already been set to a low frequency, then according to the interleaving anti-interference rule, CH2 must avoid the low-frequency range. In this case, simply set DIP 6 on S2 to OFF and DIP 7 to OFF as well; CH2 will instantly shift to the high-frequency band, thereby ensuring interference-free operation between the front and rear coils within the same detector.
4-Step Frequency Selection Table
To help field technicians quickly configure the DIP switches within the confined space of a barrier gate enclosure, we have condensed the LD-200 dual-channel, independent four-step frequency tuning matrix into the following practical quick-reference table:
| Set the Frequency Level (Frequency) | Front Channel CH1 DIP Switch Settings (Controlled by S1) | Front Channel CH1 DIP Switch Settings (Controlled by S1) | Recommendations for On-Site Engineering Applications |
| High (High) | DIP 9 = OFF / DIP 10 = OFF | DIP 9 = OFF / DIP 10 = OFF | Operate as a single, independent channel; or use as a high-frequency barrier when adjacent channels are set to low frequency. |
| Medium-High (Medium-High) | DIP 9 = ON / DIP 10 = OFF | DIP 9 = ON / DIP 10 = OFF | Suitable for four lanes arranged side-by-side, serving as secondary high-frequency offset isolation. |
| Medium-Low (Medium-Low) | DIP 9 = OFF / DIP 10 = ON | DIP 9 = OFF / DIP 10 = ON | Suitable for four lanes arranged side-by-side, serving as secondary low-frequency offset isolation. |
| Low (Low) | DIP 9 = ON / DIP 10 = ON | DIP 9 = ON / DIP 10 = ON | Deploy immediately adjacent to high-frequency coils to eliminate cross-frequency interference. |
(Important Engineering Note: Each time you use a screwdriver to change the frequency DIP switches on S1 or S2, be sure to firmly press the Reset button located directly below the panel to force the microprocessor to rescan the underlying reference frequency. If you adjust the DIP switches while the power is on without resetting, the new frequency will not take effect!)
Decoding Digital Sensitivity (Pitfall 2)
After resolving the major issue of frequency crosstalk, the next tricky challenge facing field engineers is “missed detections” and “false positives.” When configuring sensitivity, many newcomers to the field are highly prone to falling into a second critical pitfall (Pitfall 2): blindly trusting vague marketing claims in the manual—such as “extremely high sensitivity”—while overlooking the underlying physical logic behind the detection mechanism. True industrial-grade vehicle detectors never rely on vague adjectives; instead, they use extremely stringent inductance change rate parameters for digital definition.
If you examine the LD-200’s technical manual closely, you’ll find that its maximum sensitivity is precisely specified as 0.015%. Behind this seemingly dry number lies the extremely high-precision measurement capability of an industrial-grade instrument.

What Does 0.015% Inductance Change Mean?
What does this mean? When a vehicle drives over the loop, the metal in its chassis absorbs magnetic field energy, causing a decrease in the total inductance of the entire underground loop. The 0.015% specification indicates that the microprocessor can precisely detect an extremely faint disturbance—amounting to just “one-tenth of one percent” of the total ambient inductance. This level of resolution enables the system to easily detect not only heavy steel trucks but even lightweight off-road vehicles with extremely high chassis and all-aluminum bodies, or even motorcycles whose tires merely graze the coil—as long as they cause a magnetic field fluctuation of 0.015%, the system will instantly trigger a response. Relying on hard, concrete numerical metrics is the core guarantee for eliminating vehicle detection failures.
Adapting Sensitivity to High-Clearance Chassis
What practical value do these extremely high-precision parameters offer in real-world applications? Let’s examine one of the most frustrating engineering challenges in logistics parks: when container semi-trailers or heavy-duty trucks with high chassis slowly pass through toll booth barriers, the barrier arm suddenly drops prematurely—even before the vehicle’s long body has fully cleared the lane—and strikes the cargo compartment.
The cause of this “mid-pass barrier drop” is precisely the physical limitation imposed by chassis height. The farther the vehicle’s chassis is from the ground-mounted loop, the weaker the metal’s effect on the magnetic field, resulting in a sharp decrease in the rate of inductance change detected by the system. Furthermore, semi-trailers often have large open spaces between the front and rear wheels (the highest point on the chassis with no metal components at all). If the detector is not sensitive enough, the system will misinterpret this “magnetic field blind spot” as “the vehicle has completely cleared the area,” thereby erroneously issuing a command to lower the barrier.
Therefore, at entry and exit points where mixed vehicle types pass through, you must never rigidly apply standards designed for passenger cars. To prevent heavy-duty trucks from being struck by the barrier, on-site technicians must configure a dedicated, independent, and highest-level sensitivity setting specifically for these high-clearance chassis vehicles, forcibly raising the detector’s sensitivity threshold to ensure that the relay remains firmly locked in the closed position until the massive vehicle has completely cleared the barrier.
8-Level Sensitivity Configuration Guide
When faced with complex mixed lanes containing everything from passenger cars to heavy semi-trailers and light off-road vehicles, traditional “single-knob blind adjustment” devices often fail to address all scenarios effectively. To thoroughly address the issue of missed detections caused by differences in chassis height, the LD-200 / LD-202 has abandoned the crude analog potentiometer design and equipped the front and rear coils with completely independent, 8-level high-precision digital sensitivity adjustment matrices.
S1 (D6-D8) Settings for CH1 Sensitivity
The trigger threshold for the front ground-loop coil (CH1) is entirely controlled by switches D6, D7, and D8 in the main DIP switch group S1 (Switch 1) on the control box panel.
By combining the ON and OFF positions of these three physical DIP switches, field engineers can define CH1’s sensitivity to metal with extreme precision. The adjustment range is extremely broad, spanning from an extremely sensitive 0.015% (Highest) all the way to the least sensitive 0.8% (Lowest). If the lane you are currently commissioning requires anti-crushing protection specifically for large container trucks with low chassis, simply set D6, D7, and D8 all to ON, and CH1 will immediately enter the 0.015% maximum detection state.
S2 (D3-D5) Settings for CH2 Sensitivity
Completely decoupled from CH1, the sensitivity parameters for the rear ground-loop coil (CH2) are independently mapped to D3, D4, and D5 of the secondary DIP switch group S2 (Switch 2).
The greatest engineering advantage of this dual-channel physically isolated control lies in “asynchronous adaptation.” During actual installation, you can assign completely different detection logics to the two loops within the same system. For example: Set CH1, which is responsible for collision detection, to extremely high sensitivity to ensure that no large vehicle is missed; simultaneously, set CH2, which is responsible for passage and billing, to a medium-to-low sensitivity of 0.08% or even 0.12%, thereby effectively filtering out false triggers caused by pedestrians pushing carts, moving metal trash cans, or electric bikes approaching from the adjacent non-motorized vehicle lane.
8-Level Sensitivity Matrix
To enable frontline electrical installers to quickly and accurately configure independent sensitivity settings for both channels without having to consult a thick manual, we have condensed the LD-200’s underlying 8-level inductance change rate parameters into the following on-site quick reference table:
| Target Sensitivity (Sensitivity %) | CH1 DIP Switch Matrix (S1: D6 / D7 / D8) | CH2 DIP Switch Matrix (S2: D3 / D4 / D5) | Practical Engineering Recommendations |
| 0.015% (Highest) | ON / ON / ON | ON / ON / ON | Specifically designed to prevent the barrier from dropping mid-cycle and causing accidents involving various high-chassis semi-trailers and heavy-duty trucks. |
| 0.02% | ON / ON / OFF | ON / ON / OFF | Suitable for dedicated lanes for off-road vehicles and SUVs with high chassis. |
| 0.04% | ON / OFF / ON | ON / OFF / ON | Recommended sensitivity setting for mixed-traffic lanes, balancing sensitivity and interference resistance. |
| 0.08% | ON / OFF / OFF | ON / OFF / OFF | Suitable for dedicated entry and exit lanes for standard passenger cars. |
| 0.12% | OFF / ON / ON | OFF / ON / ON | Suitable for scenarios where pedestrians walk alongside the lane and protection against metal interference is required. |
| 0.2% | OFF / ON / OFF | OFF / ON / OFF | Medium-to-low sensitivity, used to reliably eliminate false alarms caused by non-motorized vehicles. |
| 0.5% | OFF / OFF / ON | OFF / OFF / ON | Extremely low sensitivity, reacts only to large areas of heavy metal in close contact with the ground. |
| 0.8% (Lowest) | OFF / OFF / OFF | OFF / OFF / OFF | Lowest sensitivity setting, typically used in special, harsh testing environments with strong interference. |
Hardware Isolation: The Importance of Feeder Twisting
Once you’ve configured the frequency DIP switches and sensitivity settings inside the control box, you’ve only won half the battle against multi-channel interference. In real-world engineering projects, another hidden culprit—one that most easily triggers “phantom false alarms” yet is frequently overlooked by installation crews—often lurks inside underground conduit: the section of wire running from the edge of the ground-loop coil all the way to the detector base, known in the industry as the feeder cable.

The “20 Twists Per Meter” Electrical Standard
To save time, many non-professional installers often simply pull two parallel standard wires directly into the barrier gate control box when laying cables. This practice is extremely dangerous in electrical engineering. If the feeder cable is not twisted into a twisted-pair configuration, this long stretch of parallel wires immediately becomes, in physical terms, an extremely sensitive “receiving antenna,” frantically picking up stray radio waves in the air as well as alternating magnetic fields leaking from adjacent lanes.
To eliminate this “antenna’s” ability to receive signals at the physical level, the industry has a mandatory construction standard that must be strictly followed: all feeder cables—from the edge of the road cut all the way to the terminal blocks inside the control cabinet—must be tightly twisted into a twisted-pair configuration. Furthermore, engineering standards explicitly require that the twisting density must reach “at least 20 twists per meter (20 Twists Per Meter).” Only by achieving this physical twisting density can the feeder section be considered to have truly donned its physical armor against crosstalk.
Canceling Common-Mode Noise in Conduits
Why does the simple act of “twisting wires together” produce such a powerful anti-interference effect? The core principle behind this is the physical phenomenon of current cancellation.
In narrow underground conduits, ground-sensing feeders are often unavoidably forced to share the same confined space with the 110V/220V power cables for barrier gate motors. When high-voltage cables are frequently turned on and off, they radiate strong electromagnetic interference (EMI, or common-mode noise). When the two feeders are tightly twisted together to form a braided structure, the interference currents induced by the external strong electromagnetic field in the two conductors are exactly equal in magnitude; however, due to the alternating spiral structure, the physical directions of these two currents are exactly opposite.
During high-speed data transmission, these two opposing interference currents instantly “cancel each other out” at every twisted node. This powerful common-mode rejection capability ensures that even in extremely harsh environments with high-voltage interference, the detector’s microprocessor still receives an exceptionally clean, true coil-cutting signal, providing complete immunity to noise spikes from surrounding electrical equipment.
Grounding & Shielding for Industrial Toll Plazas
In complex electrical environments such as the entrances to large industrial parks or heavy-duty toll plazas, the space is not only filled with magnetic fields from adjacent coils but also interspersed with electromagnetic pulses generated when high-power motors start up. To remain unaffected by these extreme electromagnetic storms, in addition to the twisted-pair interference suppression mentioned earlier, field engineers must also maintain the final line of physical defense: extremely strict grounding and shielding standards.

Utilizing Pin 9 Chassis Ground
When troubleshooting faulty enclosures that frequently experience “phantom barrier drops,” we often encounter a common installation oversight: installers connect only the power and coil wires, leaving the ground pin on the 11-pin socket completely floating.
For high-precision industrial-grade detectors like the LD-200, Pin 9 (Chassis Ground) on the 11-pin socket is by no means an optional terminal. This chassis ground pin serves as the sole discharge path for the entire microprocessor to dissipate static electricity, lightning surges, and common-mode interference. Engineering principles strictly dictate that Pin 9 must never be left floating. When wiring on-site, you must use a yellow-green wire of sufficient gauge to securely connect Pin 9 to the control cabinet’s physical ground bus (Earth Ground), ensuring that all stray interference charges are instantly dissipated into the ground, thereby guaranteeing the absolute stability of the motherboard’s operation.
Proper Shielded Cable Termination
When the physical distance between the detector and the ground coil is significant—especially when the feedline exceeds 10 meters—standard twisted-pair cable is no longer sufficient to withstand long-distance signal attenuation and spatial electromagnetic interference along the route. In such cases, when selecting equipment, you should visit the Hardware & Replacement Accessories section to purchase professional shielded twisted-pair cable (Shielded Twisted Pair).
With high-quality cable, proper installation techniques are even more critical. When stripping and connecting the shield, many experienced electricians often fall into a critical electrical trap: grounding both ends of the shield (the coil end and the control box end) simultaneously.
Engineering specifications strictly warn: the shield must only be “single-ended grounded”! The correct procedure is to connect the shielding mesh to the chassis ground (Pin 9) only on the control cabinet side. At the connection point of the underground coil, the shielding mesh must be cut and thoroughly wrapped with electrical tape to keep it floating.
If you mistakenly implement dual-end grounding, the shielding mesh will physically form a massive “ground loop” due to the potential difference that often exists between the underground coil end and the control cabinet end. Not only does this loop fail to provide shielding, but it actually acts as a super-sensitive receiving antenna, continuously drawing stray currents from the ground into the detector, which directly causes a complete collapse of the vehicle loop detector’s crosstalk frequency parameters. Therefore, strictly adhering to the principle of single-ended shielding is the key to building a zero-interference multi-lane defense system.
Diagnostic LEDs: Identifying Inductance Faults
When troubleshooting signal distortion and interference issues at multi-lane sites, field engineers do not need to rely on a multimeter to blindly guess the status of the underlying inductors. The LD-200 panel is equipped with highly intuitive Diagnostic LEDs that translate the physical health status of underground coils into visible flashing codes in real time. Understanding these codes is essential for quickly troubleshooting faults related to vehicle loop detector crosstalk frequency.
Translating Green LED Blinking Codes
Based on the device’s underlying technical troubleshooting logic, both the front CH1 and rear CH2 are equipped with independent green detection LEDs. By observing the blinking pattern of this green LED, you can instantly pinpoint the source of a physical fault in the underground loop:
Green LED Steady On: This is a completely normal operating state, indicating that the system is detecting a vehicle’s metal profile in a steady state.
Green LED Blinking Slowly: This is a clear warning of low inductance. It directly indicates that the underground loop for the current channel may have a physical short circuit, or that the number of twists in the twisted-pair feedline extending from the loop is severely insufficient.
Green light blinking fast: This indicates a signal loss or excessive inductance warning. It suggests that the underground coil may have been severed (open circuit), or that the number of coil windings or the number of twists in the twisted-pair feedline is excessively high.
Adjusting Turns Based on Frequency Warnings
When the green light on the panel flashes erratically to signal a frequency warning, how can the site quickly remedy the issue at the lowest possible cost? The technical manual provides a standard intervention procedure:
If the system’s green light flashes slowly (indicating insufficient turns), this essentially means that the total inductance of the current coil is too low, causing the ambient reference frequency to spike excessively high. Before deciding to re-excavate the road surface to increase the physical number of turns, you should first use the DIP switches inside the control box to forcibly lower the operating frequency of that channel. If the green light stops flashing (remains steady) after forcibly lowering the frequency via the DIP switches, the issue is resolved; however, if it continues to flash slowly after the frequency reduction, this indicates that the physical inductance has exceeded the chip’s tolerance limit, and you must re-excavate the road surface to add more coil turns.
Conversely, if the system experiences rapid flashing of the green light (indicating too many turns), the underlying issue is that the frequency has been set too low. In this case, you should use the DIP switches to forcibly increase the frequency (the higher the frequency) to attempt to resolve the fault; if electronic tuning fails, you must remove the excess coil turns.
To eliminate these frequency alarms and rework caused by “non-standard winding” at the engineering source, we strongly recommend that construction teams use industrial-grade wiring and prefabricated components that meet standard impedance requirements directly during the civil engineering phase. You can visit the Loop Detectors & Coils section to review the specifications for standardized coils—including their inductance and number of turns—to ensure that road cutting and paving are completed correctly the first time, thereby minimizing the rate of electromagnetic failures later on.
Vehicle Loop Detector Crosstalk FAQ
When performing on-site commissioning for multi-lane parallel configurations and complex toll islands, field technicians often have questions about the configuration of frequency parameters and system logic. The following summarizes the three key practical Q&As regarding vehicle loop detector crosstalk frequency to help your team completely avoid common engineering pitfalls.
Can I set both loops to high frequency if I need a fast response?
Engineering Conclusion: Absolutely not.
Many novice engineers fall into a serious misconception, believing that “the higher the frequency, the faster the barrier arm will rise.” In fact, the operating frequency of the induction loop (high, medium-high, medium-low, low) has no physical correlation with the trigger response speed of the relay; it is merely an anti-interference tool used for “electromagnetic frequency isolation.”
If, on two adjacent lanes, you set both detectors to “High” in pursuit of so-called “fast response,” not only will they not become faster, but the complete overlap of frequencies will instantly trigger severe intermodulation distortion underground. This practice will cause the microprocessor to become completely disoriented in the chaotic magnetic field, directly leading to the complete failure of the anti-crushing system and frequent “phantom barrier drops.”
Why isn’t the new frequency setting working?
Cause of the problem: You omitted the forced reload step after modifying the parameters.
When troubleshooting live on-site, many technicians use a screwdriver to toggle the frequency switches on S1 or S2. If they find that the interference persists, they mistakenly assume the device is faulty. In reality, the MCU cache inside the detector does not automatically refresh in real time to reflect changes made to the physical panel’s DIP switches.
Here is a golden rule of debugging that must be followed: Every time you modify any DIP switch on the panel, you must use an insulated tool to press the Reset button beneath the panel to perform a hard reset (The LD-200 must be reset every time a setting change is made to the DIP switches). Only after performing a hardware reset will the microprocessor clear the old interference data and rescan the underground coil according to the new frequency parameters you have just set.
How does this relate to direction detection?
Underlying Logic: Frequency tuning is the hardware foundation for all advanced security algorithms.
Many people wonder: What does frequency isolation have to do with complex anti-tailgating logic? You can think of frequency tuning as the foundation of a building. In dense, multi-lane environments, if there is severe crosstalk between adjacent loops, the microprocessor receives nothing but jittery and chaotic signals. It cannot even accurately determine the most basic question—“Is there a vehicle in the current lane?”—let alone precisely calculate the order in which vehicle fronts cross the lane lines.
Only by adhering to strict frequency interleaving rules—ensuring that each channel’s reference frequency is pure and free from interference—can the advanced phase-based anti-tailgating logic (Modes 1 through 3) of the dual-channel loop detector direction detection system, which we explained in depth in our previous guide, obtain the most accurate raw data inputs. This enables 100% precise execution of anti-crushing and interception tasks.